Enhance your heating, cooling, and water circulation applications with the Taco 0011-SF4-IFC Stainless Steel Cartridge Circulator Pump. Optimally designed for both commercial and residential setups, this circulator ensures robust fluid movement and superior performance.
Routinely used across hydronic heating, chilled water, and solar heating systems, this circulator is appreciated for its compact design and ease of installation. Its stainless steel construction not only provides durability but also resists corrosion over time.
Brand | Taco |
---|---|
MPN | 0011-SF4-IFC |
Power | 1/8 HP |
Voltage | 115V |
Flow Rate | Up to 30 GPM |
Head Range | Up to 31 feet |
Max Pressure | 125 PSI |
Connection Size | 3/4", 1", 1-1/4", 1-1/2" |
Connection Type | Flanged x Flanged |
Material | Stainless Steel |
High Performance: Delivers up to 31 GPM with 31 feet of head, ideal for medium-head, high-flow applications.
Durable Stainless Steel Construction: Built to resist corrosion and provide long-lasting performance in demanding environments.
Integral Flow Check (IFC): Includes a built-in check valve to prevent reverse flow, reducing the need for additional components and simplifying installation.
Versatile Applications: Perfect for hydronic heating, radiant heating, hydro-air fan coils, indirect water heaters, and domestic hot water recirculation.
Low Maintenance: The replaceable cartridge system simplifies service by consolidating all moving parts in one easy-to-maintain component.
Q: What is the Taco 0011-SF4-IFC?
A: The Taco 0011-SF4-IFC is a stainless steel, in-line cartridge circulator pump designed for high-head, medium-flow applications in hydronic heating and chilled water systems. It features an integral flow check (IFC) for improved performance and ease of installation.
Q: Where is it typically used?
A: The Taco 0011-SF4-IFC is used in large residential and light commercial hydronic heating systems, chilled water cooling systems, and domestic hot water recirculation applications.
Q: Is it easy to install?
A: Yes, the pump is designed for easy installation with flanged connections and an integral flow check that simplifies the setup by removing the need for an additional flow check valve.
System Preparation:
Ensure the system is filled with clean water or a maximum 50% propylene-glycol solution before operating the pump. The pump's water-lubricated bearings must not run dry.
Air Purging:
Use the pump’s built-in air purging feature to eliminate air. If air remains, manually vent the system to prevent noise and inefficiency.
Routine Inspection:
Regularly check for abnormal noise or vibrations, which could indicate cavitation or debris in the impeller.
Cartridge Maintenance:
The 0011-SF4-IFC has a replaceable cartridge containing all moving parts. If the pump shows reduced performance, consider replacing the cartridge.
Electrical Checks:
Ensure electrical connections are secure, and verify the power supply matches the pump's requirements.
Environmental Considerations:
Install the pump in a dry, indoor location and avoid using petroleum-based fluids or chemical additives to prevent internal component damage.
Installation Best Practices:
Mount the pump with vibration dampeners and rotate the control cover as needed for flexible installation.